Air Scrubber Sizing Calculation: CFM, ACH, and Unit Count for Air Filtration Projects
Calculate the required CFM and number of HEPA air scrubber units for any room based on volume and target air changes per hour. Size air scrubbers for mold remediation, construction dust control, and indoor air quality projects.
Related Calculators
Air Scrubber Basics
An air scrubber (also called a negative air machine or air filtration device) circulates room air through HEPA and carbon filters to remove particulate matter, mold spores, dust, and VOCs.
Key sizing parameter: Air Changes per Hour (ACH)
ACH = (Scrubber CFM × 60) / Room volume in cubic feet
Required scrubber CFM = (Required ACH × Room volume) / 60
ACH Requirements by Application
Worked Sizing Example
Room: 20 ft × 30 ft × 9 ft = 5,400 cubic feet
Target: 6 ACH for mold remediation containment
Required CFM = (6 × 5,400) / 60 = 32,400 / 60 = 540 CFM
Select an air scrubber rated for ≥ 540 CFM → choose 500–600 CFM unit or run two 300 CFM units.
Unit count calculation: Unit count = Required CFM / (Unit rated CFM × Derating factor)
For 500 CFM unit at 80% derating: 540 / (500 × 0.80) = 540 / 400 = 1.35 → 2 units
Common Air Scrubber Models and Capacities
Negative Air Pressure for Containment
For containment work (mold, asbestos, lead): the air scrubber exhausts air outside the containment area to create negative air pressure, preventing contaminants from escaping.
Negative air pressure requirement: - 0.02–0.03 in. W.G. (water gauge) pressure differential - Exhaust the air outside the building or to a HEPA-filtered exhaust port - Replace makeup air through filtered inlets
Filter Types in Air Scrubbers
Frequently Asked Questions
- How many air changes per hour does mold remediation require?
- IICRC S520 (Standard for Professional Mold Remediation) recommends a minimum of 4 air changes per hour in remediation work areas. During active disturbance (tearing out moldy materials), higher ACH of 6–8 is recommended to control airborne spore concentrations. For containment setup prior to remediation: establish negative air pressure with at least 4 ACH as a baseline. The negative pressure (−0.02 to −0.03 in. W.G.) prevents contaminated air from migrating to clean areas. HEPA filtration at the air scrubber exhaust captures spores before exhausting air outside the containment.
- What size air scrubber do I need for a 1,500 square foot space?
- For a 1,500 sq ft space with 9-foot ceilings: volume = 1,500 × 9 = 13,500 cubic feet. At 6 ACH (standard renovation): CFM = (6 × 13,500) / 60 = 1,350 CFM. You'd need two 600–700 CFM air scrubbers running simultaneously, or one 1,500 CFM industrial unit. For basic air quality improvement at 4 ACH: CFM = (4 × 13,500) / 60 = 900 CFM — single large unit or two medium units. Consider ceiling height when sizing — 10-foot ceilings increase volume by 11%, requiring proportionally more CFM.
- What is the difference between a negative air machine and an air scrubber?
- Functionally, a negative air machine and an air scrubber are the same device — a HEPA-filtered blower. The difference is in how they're used: As a 'negative air machine': air is exhausted outside the containment area to create negative pressure inside the containment zone, preventing contaminated air from leaking out. As an 'air scrubber': air is recirculated within the space through the HEPA filter to clean the room air without pressurizing or depressurizing the space. For mold and asbestos remediation, negative air machine mode is required to protect adjacent areas.
- Why is the air scrubber derated below its rated CFM?
- Air scrubbers are derated from their rated airflow because rated CFM is measured with a clean filter at zero static pressure. In actual use, several factors reduce effective airflow: filter loading (a partially loaded HEPA adds 0.3–0.5 in. W.C. static pressure, reducing airflow 15–25%); ductwork when running exhaust to outside (each 10 feet of duct adds ~0.1 in. W.C.); elevated dust load in the work area (adds to filter loading faster). A 20% derating factor is standard for estimating working CFM from rated CFM. In heavily contaminated environments, use a 30–40% derating factor and plan for more frequent pre-filter changes.
Last updated 8/19/2026